022-29398436
Agriculture, forestry, animal husbandry and fishery, industrial and mining enterprises, municipal engineering,hydrology
and water conservancy, scientific research institutions, real estate and construction industry, etc
Chloride ion: it has the ability to destroy the protective film. When the dissolved oxygen in the water is too high, chloride ion will accelerate the corrosion, which is easy to cause perforation and leakage of the pipeline.
Hardness of softened water: the reason for scale formation in industrial boilers is that some calcium and magnesium salts react to form insoluble substances during water heating; The solubility of these calcium and magnesium salts decreased with the increase of water temperature, and precipitated after reaching the saturation concentration; After concentration, insoluble salt precipitation is formed. Wtf2100 boiler softened water multi parameter on-line analyzer adopts dual channel analysis design, with two sample injection valves, which can analyze chloride ion and hardness content in water before and after softening treatment in sequence. Among them, the hardness is analyzed by complexometric titration, and the detection range standard is 0-500mg / L, which can be customized according to the actual water sample; The content of chloride ion in softened water is low, and turbidimetric method is used for analysis (electrode method is suitable for measuring residual chlorine). The instrument displays the pH of the water sample in real time, and automatically analyzes the chloride ion and hardness in sequence, and uploads the analysis results through three-way analog output or communication mode. If the water sample exceeds the standard, the peripheral dosing system can be customized for treatment.
·Softened water three parameter all in one machine, highly integrated, safe and reliable, easy to use, cost saving;
·Through software setting and analysis mode adjustment, the water quality parameters before and after softening treatment are compared automatically;
·The core detection component is imported brand, which can accurately determine the titration end point;
·When the titration reaches the end point, the titration pump will stop automatically to save reagent;
·The quantitative analysis module is designed with small specifications, which saves reagents and reduces maintenance workload;
·Dynamic visualization, intuitive and convenient operation;
·Over range upper and lower limit alarm, fault alarm;
·Remote read and write data, support remote calibration and calibration;
·The software adopts hierarchical password management to ensure safe use;
·The instrument is equipped with automatic cleaning function and automatic calibration function;
·The external interface is reserved, and the expansion function can be customized according to the site conditions;
Performance parameters of wtf2100 |
|
Analysis method |
Hardness: EDTA complexometric titration chloride: turbidimetry pH: electrde method |
Analysis range |
Hardness: 0-500mg / L (extensible) chloride ion: 0-100mg / L (extensible) pH: 0-14 |
Number of samples |
2Samples |
error |
≤±3% (hardness, chloride ion);≤±0.2%(PH) |
Repeatability |
≤±3% (hardness, chloride ion); |
Zero drift |
≤±3% (hardness, chloride ion); |
Analysis frequency |
Timing analysis, interval analysis, remote control |
signal output |
4-20mA |
Communication format |
RS485 interface;Modbus Protocol |
Report output |
U disk data export to excel format |
display |
7Inch color touch screen;Bilingual |
call the police |
Isolation relay contacts |
Water production unit and pretreatment unit |
Support (optional) |
Industrial printer |
Support (optional) |
Wireless remote transmission |
Support (optional) |
Reagent consumption (single time) |
Hardness: 3ml (based on 500mg / L standard sample) chloride ion: 1ml |
Automatic cleaning |
support |
Auto calibration |
support |
Reagent cabinet / rack |
Support (optional) |
Water sample condition |
0-60℃ |
Power Supply |
AC220V 50Hz |
work environment |
5-60℃ ;Humidity < 90%, no condensation |
Dimensions |
720 * 600 * 300mm (excluding reagent cabinet) |
Gross weight |
37kg (excluding reagent cabinet) |
Cabinet protection |
IP65 corrosion resistant box material |
Installation method |
Wall mounted, vertical (can be combined with reagent cabinet) |
Software version |
ANNA1.07 |
Mean time between failures |
> 720h / time |
authentication |
ISO9000;CE |
Green ring company provides you with:
1. Water quality monitoring technical consultation and formulation of application scheme
2. Customized supporting products according to the site environment
3. Debugging and acceptance of instruments and supporting equipment
4. On site training of instrument use methods and precautions
5. After sales maintenance and repair service
Green ring company can provide customized product services for customers to meet their on-site needs. The supporting products provided by Jingxiang company include:
one Data acquisition and transmission network: remote transmission of field data to the user terminal (server, PC terminal), to achieve remote monitoring, according to the communication protocol provided by the user Develop the data format and connect with the local relevant departments.
two Analysis data PC client: through the configured computer, the analysis data will be transmitted to the computer in real time, or connected with the outdoor LED electronic LCD screen.
three Water quality regulation dosing unit: according to the instrument analysis data, real-time regulation of supporting dosing equipment, inlet and outlet valves and other third-party equipment.
four Pump control unit: it provides the control service of pump equipment on site, and can realize manual / automatic operation.
five Water quality pretreatment unit: in view of the conditions of high temperature and high pollution of water samples, it is necessary to carry out physical purification or cooling treatment
Some consumables and accessories |
||
name |
Company |
Recommended replacement cycle (6 times / day) |
Analytical reagent |
Set (1.5L) |
4Months |
Standard sample |
Set (1L) |
3Months |
Peristaltic pump pipe stuck |
root |
6Months |
Drain pipe |
root |
6Months |
Green ring promises that the reagent formula is fully open. Beijing elephant provides analytical reagents and standard samples for customers to prepare and use